Open-type transformer

EEMC manufactures three-phase open-type transformers:

– Open-type transformer, immersed in oil, adjustable at voltage 35 / 0.4; 22 / 0.4; 35/22 / 0.4; 10 / 0.4kV.

– Tested to standards.

– Products have been supplied to electricity units put into operation safely on the grid.

A transformer is an electrical device that changes the voltage of the alternating current from one level to another. Open-type transformers (with oil separators) are distributed with 35kV, 22kV, 10kV voltage, 0.4kV voltage, soaked in standard insulating oil.

Products manufactured by the Corporation, tested according to TCVN 6306-1: 2015 (IEC 60076-1: 2011) and TCVN 8525: 2015. The main raw materials are composed of: Korea; Silent wires / coated paper from copper M1; Insulating oils from Sweden, India, Malaysia. Voltage regulation from Italy. Insulating paper: Germany, Sweden. Cross-cut and cut-off circuits on G7; Wiring is performed on specialized equipment; The vacuum washer.

Photo:

Diagram:

 

TT Capacity
(kVA)
No load loss
Po (W)
Short circuit loss
Pk (W)
No load current
Io (%)
Short circuit voltage
Uk (%)
Energy efficiency
E50%
1 50 120 715 2 4-6 98.820
2 75 165 985 2 4-6 98.920
3 100 205 1250 2 4-6 98.980
4 160 280 1940 2 4-6 99.050
5 180 295 2090 2 4-6 99.100
6 250 340 2600 2 4-6 99.210
7 320 385 3170 2 4-6 99.270
8 400 433 3820 2 4-6 99.310
9 500 525 4440 2 4-6 99.350
10 560 580 4810 2 4-6 99.370
11 630 780 5570 2 4-6 99.320
12 750 845 6540 2 4-6 99.340
13 800 872 6942 2 4-6 99.350
14 1000 980 8550 2 4-6 99.380
15 1250 1115 10690 2 4-6 99.400
16 1500 1250 12880 1.5 4-6 99.410
17 1600 1305 13680 1.5 4-6 99.410
18 1800 1400 15400 1 5-7 99.420
19 2000 1500 17100 1 5-7 99.430
20 2500 1850 21000 1 5-7 99.440

Leave a Reply